Tyco Fire Protection Products

Model TY-B - Upright, Pendent, and Recessed Pendent Sprinklers

From

0

The TYCO Series TY-B, 2.8, 5.6, and 8.0 K-factor, Upright and Pendent Sprinklers described in this data sheet are standard response - standard coverage, decorative 5 mm glass bulb type spray sprinklers designed for use in light, ordinary, or extra hazard, commercial occupancies such as banks, hotels, shopping malls, factories, refineries, and chemical plants. The recessed version of the Series TY-B Pendent Sprinkler, where applicable, is intended for use in areas with a finished ceiling. It uses a two-piece Style 10 (1/2 inch NPT) or Style 40 (3/4 inch NPT) Recessed Escutcheon. The Recessed Escutcheon provides 1/2 inch (12,7 mm) of recessed adjustment or up to 3/4 inch (19,1 mm) of total adjustment from the flush pendent position. The adjustment provided by the Recessed Escutcheon reduces the accuracy to which the fixed pipe drops to the sprinklers must be cut.

Features:

  • All hazard
  • Discharges a hemispherical water spray pattern in the area beneath the sprinkler
  • Small frame, narrow profile bulb
  • Designed for use in light, ordinary, or extra hazard, commercial occupancies such as banks, hotels, shopping malls, factories, refineries, chemical plants, etc.

Hazard: All
Temperature: 135, 155, 175, 200, 286, 360, Open
Thread: 1/2',3/4'
Approval: UL, C-UL, FM, LPCB, NYC, VdS
Response: Standard Response
SIN Numbers: TY1151,TY1251,TY3151,TY3251,TY4851,TY4951,TY4151,TY4251
Wrench: W6
Wrench [Recessed]: W7

Corrosion resistant coatings, where applicable, are utilized to extend the life of copper alloy sprinklers beyond that which would otherwise be obtained when exposed to corrosive atmospheres. Although corrosion resistant coated sprinklers have passed the standard corrosion tests of the applicable approval agencies, the testing is not representative of all possible corrosive atmospheres. Consequently, it is recommended that the end user be consulted with respect to the suitability of these coatings for any given corrosive environment. The effects of ambient temperature, concentration of chemicals, and gas/chemical velocity, should be considered, as a minimum, along with the corrosive nature of the chemical to which the sprinklers will be exposed.

An intermediate level version of the Series TY-B Pendent Sprinkler can be obtained by utilizing the Series TY-B Pendent Sprinkler in combination with the Model S2 Shield.

Sprinkler Identification Numbers

TY1151: Upright 2.8K, 1/2˝ NPT
TY1251: Pendent 2.8K, 1/2˝ NPT
TY3151: Upright 5.6K, 1/2˝ NPT
TY3251: Pendent 5.6K, 1/2˝ NPT
TY4151: Upright 8.0K, 3/4˝ NPT
TY4251: Pendent 8.0K, 3/4˝ NPT
TY4851: Upright 8.0K, 1/2˝ NPT
TY4951: Pendent 8.0K, 1/2˝ NPT

Approvals
UL and C-UL Listed
FM, LPCB, VdS, and NYC Approved (Refer to Table A for complete approval information including corrosion resistant status.)

Maximum Working Pressure
Refer to Table B

Discharge Coefficient
K = 2.8 GPM/psi1/2 (40,3 LPM/bar1/2)
K = 5.6 GPM/psi1/2 (80,6 LPM/bar1/2)
K = 8.0 GPM/psi1/2 (115,2 LPM/bar1/2)

Temperature Ratings
Refer to Table A

Finishes
Sprinkler: Refer to Table C
Recessed Escutcheon: Signal or Pure White, Jet Black, Chrome Plated, or Natural Brass

Physical Characteristics
Frame: Bronze
Button: Brass/Copper
Sealing Assembly: Beryllium Nickel w/TEFLON
Bulb: Glass
Compression Screw: Bronze
Deflector: Copper
Bushing (K = 2.8): Bronze

Operation
The glass bulb contains a fluid which expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass bulb, allowing the sprinkler to activate and water to flow.

Design Criteria
The TYCO Series TY-B, 2.8, 5.6, and 8.0 K-factor, Upright and Pendent Sprinklers are intended for fire protection systems designed in accordance with the standard installation rules recognized by the applicable Listing or Approval agency (for example, UL Listing is based on the requirements of NFPA 13, and FM Approval is based on the requirements of the FM Loss Prevention Data Sheets). Only the Style 10 or 40 Recessed Escutcheon, as applicable, is to be used for recessed pendent installations.