Tyco Fire Protection Products

Model TY-L - Upright, Pendent, and Recessed Pendent Sprinklers

From

0

The TYCO Series TY-L, 5.6 and 8.0 K-factor, Upright and Pendent Sprinklers described in this data sheet are standard response -standard coverage, solder type spray sprinklers designed for use in light, ordinary, and extra hazard, commercial occupancies such as banks, hotels, shopping malls, factories, refineries, chemical plants, etc. The recessed version of the Series TY-L Pendent Sprinkler, where applicable, is intended for use in areas with a finished ceiling. It uses a two-piece Style 20 (1/2 inch NPT) or Style 30 (3/4 inch NPT) Recessed Escutcheon. The Recessed Escutcheon provides 1/4 in. (6,4 mm) of recessed adjustment or up to 1/2 in. (12,7 mm) of total adjustment from the flush pendent position. The adjustment provided by the Recessed Escutcheon reduces the accuracy to which the fixed pipe drops to the sprinklers must be cut.

Features:

  • All hazards
  • Discharges a hemispherical water spray pattern in the area beneath the sprinkler
  • Designed for use in light, ordinary, and extra hazard, commercial occupancies such as banks, hotels, shopping malls, factories, refineries, chemical plants, etc.

Hazard: All
Temperature: 165, 212, 280
Thread: 1/2',3/4'
Approval: UL, C-UL, FM, LPCB
Response: Standard Response
SIN Numbers: TY3111,TY3211,TY4111,TY4211,TY4811,TY4911
Wrench: W9
Wrench [Recessed]: W10

Corrosion resistant coatings, where applicable, are utilized to extend the life of copper alloy sprinklers beyond that which would otherwise be obtained when exposed to corrosive atmospheres. Although corrosion resistant coated sprinklers have passed the standard corrosion tests of the applicable approval agencies, the testing is not representative of all possible corrosive atmospheres. Consequently, it is recommended that the end user be consulted with respect to the suitability of these coatings for any given corrosive environment. The effects of ambient temperature, concentration of chemicals, and gas/chemical velocity, should be considered, as a minimum, along with the corrosive nature of the chemical to which the sprinklers will be exposed.

An intermediate level version of the Series TY-L Pendent Sprinkler can be obtained by utilizing the Series TY-L Pendent Sprinkler in combination with the Model S Shield.

Sprinkler Identification Number (SIN)

TY3111: Upright 5.6K, 1/2” NPT
TY3211: Pendent 5.6K, 1/2” NPT
TY4111: Upright 8.0K, 3/4” NPT
TY4211: Pendent 8.0K, 3/4” NPT
TY4811: Upright 8.0K, 1/2” NPT
TY4911: Pendent 8.0K, 1/2” NPT

TY3111 is a re-designation for S1800 and G3111.
TY3211 is a re-designation for S1801 and G3112.
TY4111 is a re-designation for S1810 and G3101.
TY4211 is a re-designation for S1811 and G3102.
TY4811 is a re-designation for S1805.
TY4911 is a re-designation for S1806.

Approvals
UL and C-UL Listed. FM, and LPCB Approved. (Refer to Table A for complete approval information including corrosion resistant status.)

Maximum Working Pressure
175 psi (12,1 bar)

Discharge Coefficient
K=5.6 GPM/psi1/2 (80,6 LPM/bar1/2)
K=8.0 GPM/psi1/2 (115,2 LPM/bar1/2)

Temperature Ratings
Refer to Table A

Finishes
Sprinkler: Refer to Table A Recessed
Escutcheon: White Coated, Chrome Plated, or Brass Plated

Physical Characteristics
Frame: Brass
Sealing Button: Bronze w/TEFLON
Ejection Spring: Stainless Steel
Fusible Element: Solder, Copper, Stainless Steel
Strut: Monel
Hook: Bronze/Monel
Deflector: Bronze

Operation
A copper tube sealed by two stainless steel balls holds a fusible alloy. When the rated temperature is reached, the alloy melts, the balls are forced toward each other releasing the tension mechanism, allowing the sprinkler to operate.

Design Criteria
The TYCO Series TY-L, 5.6 and 8.0 K-factor, Upright and Pendent Sprinklers are intended for fire protection systems designed in accordance with the standard installation rules recognized by the applicable Listing or Approval agency (e.g., UL Listing is based on the requirements of NFPA 13, and FM Approval is based on the requirements of FM’s Loss Prevention Data Sheets). Only the Style 20 or 30 Recessed Escutcheon, as applicable, are to be used for recessed pendent installations.